AS/NZS 5601 Gas Standards — Key Clauses for Residential Plumbing & Gas Work
What Is AS/NZS 5601?
AS/NZS 5601 covers the design, installation, commissioning, and maintenance of gas installations. It applies to natural gas (NG) and liquefied petroleum gas (LPG) systems in residential, commercial, and industrial settings. For QLD gas fitters, compliance is mandatory under the Petroleum and Gas (Production and Safety) Act 2004.
The Two Parts
| Part | Title | Scope |
|---|---|---|
| Part 1 | General Installations | Pipe sizing, materials, installation methods, testing, commissioning, ventilation, clearances, appliance connections |
| Part 2 | LP Gas Installations in Caravans and Boats | Specific requirements for mobile/marine LP gas systems (less common for residential plumbers) |
Critical Clauses for Residential Gas Work
Gas Meter Clearances (Clause 5.3)
| From | Minimum Clearance |
|---|---|
| Openable windows/doors | 500mm |
| Sources of ignition | 1000mm |
| Electrical switchboards/meters | 500mm (or separated by non-combustible barrier) |
| Ground level | Minimum 150mm above finished ground |
Gas Pipe in Wall Cavities (Clause 5.5.3)
Gas piping installed in wall cavities must be:
- A continuous length without joints within the cavity
- Enclosed in a gas-tight sleeve where passing through floors or fire-rated walls
- Protected from physical damage (nail plates where within 50mm of stud face)
- Copper or stainless steel (not PE or composite in cavities)
Testing Pressures (Clause 7.2)
| Test Type | Pressure | Duration | Acceptable Result |
|---|---|---|---|
| Strength test (new install) | 10 kPa (NG) / 20 kPa (LPG) | 3 minutes minimum | No pressure drop |
| Tightness test | Operating pressure (2.75 kPa NG) | 3 minutes minimum | No pressure drop |
| Purging | Operating pressure | Until gas detected at outlet | Confirm gas presence, check for leaks |
Ventilation for Gas Appliances (Clause 6.4)
All gas appliances require adequate ventilation for combustion air and flue gas dispersal:
- Type A appliances (room-sealed/balanced flue) — No additional room ventilation required
- Type B appliances (open-flued) — Permanent ventilation openings required, sized based on appliance input rating
- Unflued appliances — Maximum 10 MJ/h input in a room, openable window required, not in bedrooms or bathrooms
LPG Cylinder Location (Clause 5.11)
- Minimum 1m from any opening (window, door, air intake) below the level of the cylinder relief valve
- Minimum 2m from any drain, pit, or below-ground area
- Not under a building unless specifically designed enclosure
- Protected from vehicle impact if near driveways
When Do You Need to Lodge a Form?
In QLD, most gas work is notifiable work requiring a Form 7 lodgement with your local council within 5 business days of completion. This includes new gas installations, alterations to existing gas systems, and gas appliance connections (except like-for-like replacements in the same location).